Centrale conventionale de mici dimensiuni

FACP ES Line for 8 zones

8 sensor groups with up to 32 sensors in each sensor group

Large LCD display with 8 rows x 40 characters

Integrated sensor group single display

Optimized commissioning, maintenance and operation

Simple configuration and programming on the keypad

Four relays, freely programmable, non-monitored, potential free, max. 30 V DC / 2 A or 60 V DC / 1 A

2 outputs for connecting acoustic or optical sounders according to EN 54-13 (29 V DC/ max. 500 mA)

1 interface to a transmission unit for fire warnings (12 V DC / max. 200 mA)

1 interface to a transmission unit for fault warnings (12 V DC / max. 200 mA)

1 standard interface extinguisher for fire control system type C according to DIN EN 54-2

RS485 for connecting to fire department operating panel and fire department display panel

1 output UBext 29 V / 0.5A, for power supply of external bus users

72 h emergency current bridge

“Delay of relaying” function (PM operating mode according to DIN VDE 0833-2 for preventing false alarms, delay / verify)

“2-detection dependency” function (TM operating mode according to DIN VDE 0833-2 for preventing false alarms), alternatively programmable as intermediate alarm storage or 2-zone dependency between the detector zones

Alarm counter for up to 10,000 trips

Event memory for up to 10,000 events